Slice S0380.53: Elmhurst §14.0 "Main Heating SAP Code" extraction + strict-raise
Cert 000565 surfaced an Elmhurst extractor schema gap. §14.0 lodges
"Main Heating SAP Code 224" identifying Main 1 as an Air Source Heat
Pump (SAP 10.2 Table 4a row 224: "Air source heat pump, 2013 or
later") — but the extractor was dropping the line. The mapper
therefore produced a `MainHeatingDetail` with `sap_main_heating_code
= None` AND `main_heating_index_number = None` (because `PCDF boiler
Reference = 0` for HP certs), leaving the cascade to fall back to
the 0.80 gas-boiler default efficiency.
Cascade impact on cert 000565 main_heating_fuel_kwh_per_yr pin:
- Before: actual 62,375.80 kWh/yr (= 59,008 / 0.80 wrong default)
Δ +27,665.01 vs U985-0001-000565.pdf expected 34,710.79
- After: actual 29,353.32 kWh/yr (= 59,008 / 1.70 HP COP via §A4.1)
Δ −5,357.47 (remaining gap is on the space_heating side, not
heating efficiency)
The strict-raise mirrors [[unmapped-api-code]] (Slice S0380.51) and
[[unmapped-elmhurst-label]] (cylinder size / glazing type) — when
neither the §14.0 SAP code nor the PCDB boiler reference identifies
Main 1, the mapper raises `UnmappedElmhurstLabel("main_heating",
...)` so the coverage gap surfaces at extraction time instead of as
an opaque downstream SAP delta. Per user end-of-S0380.52 directive:
"if we're missing mapping on EpcPropertyDataMapper - let's raise an
exception".
Spec source: SAP 10.2 §A4 Appendix A "Heat pump cascade", Table 4a
row 224 (Air source heat pump, 2013 or later) — `seasonal_efficiency`
reads the SAP code when no PCDB Table 105/362 record overrides.
Touched:
- datatypes/epc/surveys/elmhurst_site_notes.py: `MainHeating.
main_heating_sap_code: Optional[int]` field added (treat 0 as None
per Elmhurst convention — PCDB-listed boilers lodge §14.0 SAP code
as 0 and identify themselves via the PCDB index instead)
- backend/documents_parser/elmhurst_extractor.py:
`_extract_main_heating` reads §14.0 "Main Heating SAP Code" via the
existing `_local_val` slice helper; 0/absent → None
- datatypes/epc/domain/mapper.py: `_map_elmhurst_sap_heating` passes
`sap_main_heating_code=mh.main_heating_sap_code` to
`MainHeatingDetail`, and raises `UnmappedElmhurstLabel` when
neither identifier resolves
Cohort regression check: 415 pass + 10 expected 000565 failures
(unchanged from S0380.52 — same pins, different residuals). Pyright
net-zero on all 3 touched files.
Co-Authored-By: Claude Opus 4.7 <noreply@anthropic.com>
This commit is contained in:
parent
e51fcb74ca
commit
bb9097e1a5
3 changed files with 46 additions and 0 deletions
|
|
@ -1044,6 +1044,19 @@ class ElmhurstSiteNotesExtractor:
|
|||
lines = self._section_lines("14.0 Main Heating1", "14.1 Main Heating2")
|
||||
pct_raw = self._local_val(lines, "Percentage of Heat")
|
||||
pct = int(pct_raw.split()[0]) if pct_raw else 0
|
||||
# §14.0 "Main Heating SAP Code" identifies Main 1 by SAP 10.2
|
||||
# Table 4a code (e.g. 224 = "Air source heat pump, 2013 or
|
||||
# later"). PCDB-boiler certs leave this empty / lodge "0" — the
|
||||
# PCDB index in `PCDF boiler Reference` is the identifier in
|
||||
# that case. Treat 0 (or absent) as None so the mapper can
|
||||
# distinguish "no SAP code lodged" from a real Table 4a code.
|
||||
sap_code_raw = self._local_val(lines, "Main Heating SAP Code")
|
||||
main_heating_sap_code: Optional[int] = None
|
||||
if sap_code_raw is not None:
|
||||
head = sap_code_raw.split()[0] if sap_code_raw.split() else ""
|
||||
if head.isdigit():
|
||||
v = int(head)
|
||||
main_heating_sap_code = v if v > 0 else None
|
||||
# The "Secondary Heating SapCode" key is lodged inside §14.1 Main
|
||||
# Heating2 — Elmhurst uses the Main-2 block to also carry the
|
||||
# cert's secondary heating system (when one exists). Look for it
|
||||
|
|
@ -1069,6 +1082,7 @@ class ElmhurstSiteNotesExtractor:
|
|||
percentage_of_heat=pct,
|
||||
pcdf_boiler_reference=self._local_val(lines, "PCDF boiler Reference"),
|
||||
heat_pump_age=self._local_val(lines, "Heat pump age"),
|
||||
main_heating_sap_code=main_heating_sap_code,
|
||||
secondary_heating_sap_code=secondary_code,
|
||||
)
|
||||
|
||||
|
|
|
|||
|
|
@ -3826,6 +3826,24 @@ def _map_elmhurst_sap_heating(survey: ElmhurstSiteNotes) -> SapHeating:
|
|||
heat_emitter_int = _elmhurst_heat_emitter_int(mh.heat_emitter)
|
||||
sap_control_int = _elmhurst_sap_control_code(sap_control)
|
||||
main_heating_category = _elmhurst_main_heating_category(mh, pcdb_index)
|
||||
# Strict-raise mirror of [[unmapped-api-code]] — when Main 1 has
|
||||
# neither a PCDB boiler reference nor a lodged Table 4a SAP code,
|
||||
# the mapper has no identifier for the heat source and the cascade
|
||||
# would silently fall back to the 0.80 gas-boiler default. First
|
||||
# surfaced on cert 000565 where Main 1 is a heat pump lodging
|
||||
# `PCDF boiler Reference = 0` + `Main Heating SAP Code = 224`; if
|
||||
# the extractor (or a future variant cert) drops both, raise so the
|
||||
# gap surfaces here instead of as a SAP-delta residual downstream.
|
||||
if mh.main_heating_sap_code is None and pcdb_index is None:
|
||||
raise UnmappedElmhurstLabel(
|
||||
"main_heating",
|
||||
(
|
||||
f"§14.0 Main Heating1 has neither PCDF boiler reference "
|
||||
f"({mh.pcdf_boiler_reference!r}) nor SAP code "
|
||||
f"({mh.main_heating_sap_code!r}); cannot identify the "
|
||||
f"heat source"
|
||||
),
|
||||
)
|
||||
# Shower-outlet classification: SAP10.2 Appendix J routes electric
|
||||
# showers via §J line 64a (their own kWh stream) and treats mixer
|
||||
# showers as drawing from the HW system. The Summary PDF lodges
|
||||
|
|
@ -3874,6 +3892,12 @@ def _map_elmhurst_sap_heating(survey: ElmhurstSiteNotes) -> SapHeating:
|
|||
# number drives PCDB lookup in the cascade.
|
||||
main_heating_index_number=pcdb_index,
|
||||
main_heating_data_source=1 if pcdb_index is not None else None,
|
||||
# §14.0 "Main Heating SAP Code" — Table 4a integer
|
||||
# identifying Main 1 when no PCDB boiler reference is
|
||||
# lodged (e.g. heat pump SAP code 224 on cert 000565).
|
||||
# The cascade's `seasonal_efficiency` reads this when
|
||||
# there is no PCDB Table 105/362 record to override.
|
||||
sap_main_heating_code=mh.main_heating_sap_code,
|
||||
)
|
||||
],
|
||||
has_fixed_air_conditioning=survey.ventilation.fixed_space_cooling,
|
||||
|
|
|
|||
|
|
@ -204,6 +204,14 @@ class MainHeating:
|
|||
None # e.g. "17742 Potterton, Promax 33 Combi ErP, 88.30%"
|
||||
)
|
||||
heat_pump_age: Optional[str] = None
|
||||
# Section 14.0 "Main Heating SAP Code" — the SAP 10.2 Table 4a code
|
||||
# identifying Main 1 when no PCDB boiler reference is lodged (e.g.
|
||||
# heat pump certs lodge `PCDF boiler Reference = 0` + SAP code = 224
|
||||
# for "Air source heat pump, 2013 or later"). None when the line is
|
||||
# absent or lodged as 0 (= "no code lodged"; PCDB-listed boilers
|
||||
# leave §14.0 SAP code empty and identify themselves via the PCDB
|
||||
# index instead).
|
||||
main_heating_sap_code: Optional[int] = None
|
||||
# Section 14.0 also lodges a secondary heating system (when one is
|
||||
# installed). The SAP code is the integer the cascade reads via
|
||||
# `SapHeating.secondary_heating_type` to apply the Table 11
|
||||
|
|
|
|||
Loading…