Khalim Conn-Kowlessar c0328f4e18 Slice S0380.87: SAP 10.2 Table 4e GROUP 2 HP control codes close SH +7924→+1460
SAP 10.2 Table 4e (PDF p.172-173) "Heating system controls", GROUP 2:
HEAT PUMPS WITH RADIATORS OR UNDERFLOOR HEATING:

  Code  Description                                        Type
  ----  -------------------------------------------------  ----
  2201  No time or thermostatic control                    1
  2202  Programmer, no room thermostat                     1
  2203  Room thermostat only                               1
  2204  Programmer and room thermostat                     1
  2205  Programmer and at least two room thermostats       2
  2206  Programmer, TRVs and bypass                        2
  2207  Time + temp zone control by plumbing/electrical    3   ← cert 000565
  2208  Time + temp zone control by PCDB device            3
  2209  Room thermostat and TRVs                           2
  2210  Programmer, room thermostat and TRVs               2

Pre-S0380.87 `_CONTROL_TYPE_BY_CODE` contained only Group 1 BOILER
codes (21XX); every Group 2 HP code (22XX) fell through to the
default `return 2`. Cert 000565 lodges `main_heating_control=2207`
on its HP main 1 → silently routed to type 2 → MIT_elsewhere
over-counted by ~+0.5 °C in winter.

The bug: SAP 10.2 Table 9 (PDF p.182) elsewhere off-hours differ
between type 2 and type 3:
  Type 1, 2: off-hours (7, 8) — elsewhere heated longer
  Type 3:    off-hours (9, 8) — elsewhere has separate, shorter
                                heating schedule per §9.4.14

Wrong control type → wrong off-hours → wrong off-period temperature
reduction (Table 9b) → wrong MIT_elsewhere (line (90)m) → wrong
blended MIT (line (92)/(93)m) → wrong space heating demand
(line (98c)).

Diagnosis chain: post-S0380.86 cert 000565 had structural SH
over-count of +7924 kWh independent of fabric. Diff vs worksheet
intermediates traced it to MIT cascade higher by avg +0.45 °C
(+5.42 °C-months). Per-zone breakdown showed MIT_elsewhere over by
+6.25 °C-months while Th2 setpoint matched. Reverse-engineered the
off-period reduction (cascade u≈4.12 vs worksheet u≈5.14, Jan)
matched off-hours (9, 8) — control type 3 — vs cascade (7, 8) —
control type 2. Verified against Table 4e GROUP 2 spec text:
2207 → type 3 spec-correct.

Cohort + golden + cert 9501 unaffected:
  - Elmhurst U985 cohort (000474..000516): all lodge code 2106
    (Group 1, type 2) — unchanged
  - 20 golden API certs lodge code 2206 (Group 2 HP, type 2 per
    spec, type 2 via cascade default) — adding 2206:2 to the
    dispatch dict makes the type explicit, behaviour unchanged
  - Cert 9501: not lodging 22XX codes
  - Only cert 000565 lodges 2207 (and exercises the 22XX→3 fix)

Test (1 new, AAA-structure parametrised across all 10 Group 2 codes
in `test_cert_to_inputs.py`).

**Cert 000565 closure (post-S0380.87 vs post-S0380.86):**

  Pin                    Pre      Post     Δ      worksheet
  ---                    ----     ----     ---    ---------
  sap_score              23       27       +4     29
  sap_score_continuous   22.64    27.35    +4.71  28.51
  ecf                    6.02     5.51     -0.51  5.39
  total_fuel_cost_gbp    5233     4784     -449   4680
  co2_kg_per_yr          7165     6581     -584   6448
  space_heating_kwh      66932    60468    -6464  59008
  main_heating_fuel      39372    35570    -3802  34711

Space heating residual closed +7924 → **+1460 (82% closed)**.
Integer SAP closed Δ-6 → Δ-2 (was the 9th-largest residual; now
gates only on continuous SAP rounding boundary at 28.5).

Test baseline: 561 pass (was 560 + 1 new) + 9 expected
`test_sap_result_pin[000565-*]` fails unchanged. Pyright net-zero
per touched file. SAP 10.2 spec citation included in dispatch dict
comment per [[feedback-spec-citation-in-commits]].

Per [[feedback-spec-floor-skepticism]] + [[feedback-verify-handover-claims]]:
the handover post-S0380.86 listed several candidate SH-channel
root causes (solar gains, internal gains, η, T_int, ventilation).
The single-line spec-dispatch gap was the dominant driver. The
remaining +1460 kWh residual splits roughly: ~+750 kWh from HLC
over-count (+42 W/K, mostly ventilation +27 W/K), ~+700 kWh from
remaining MIT residual.

Co-Authored-By: Claude Opus 4.7 <noreply@anthropic.com>
2026-05-30 08:59:45 +00:00
..
addresses get rid of comments 2026-05-20 13:21:11 +00:00
sap10_calculator Slice S0380.87: SAP 10.2 Table 4e GROUP 2 HP control codes close SH +7924→+1460 2026-05-30 08:59:45 +00:00
sap10_ml Slice S0380.86: §5.6 thin-wall stone + §5.8 dry-line closes BP[0] alt1 cascade gap 2026-05-30 08:37:46 +00:00
tasks added postcode splitter rewrite to ddd 2026-05-19 16:35:09 +00:00
postcode.py get rid of comments 2026-05-20 13:21:11 +00:00