SAP 10.2 §2 (17)-(18): a measured/design air permeability at 50 Pa from a
Blower Door test routes infiltration via `(18) = AP50/20 + (8)`, in
preference to the components-based (16) estimate. The Elmhurst extractor
read only the AP4 ("Pulse") column of §12.2, so a Blower Door result
(§12.2 "Pressure Test Result (AP50)") fell through to the structural-
infiltration default — over-counting ventilation heat loss.
Surfaced by simulated case 44 (AP50 4.50): effective air change rate was
0.81 vs the worksheet's 0.58 (+38% ventilation loss). The cascade already
supports `air_permeability_ap50` (preferred over AP4); this wires the read
end to end (extractor → ElmhurstSiteNotes → SapVentilation → cert_to_inputs).
Pinned against the case-44 P960 §2 at abs=1e-4: (18) infiltration 0.3417
(= 4.5/20 + 0.1167) and (25) Jan effective ach 0.5812. Worksheet harness
stays 47/47 0-raised.