Model/backend/epc_api/json_samples/real_life_examples/RdSAP-Schema-21.0.1
Jun-te Kim 5cae4a0ce5 fix(rdsap): RdSAP 10 Table 13 200/280mm solid-brick wall boundary
_u_brick_thin_wall_age_a_to_e's `<= 280` check put an uninsulated solid-
brick wall of exactly 280mm in the "200 to 280mm -> 1.7" row; RdSAP 10
§5.7 Table 13 (spec PDF p.41) shares 280 as an unlabelled edge between
that row and "280 to 420mm -> 1.4", so the table text alone doesn't say
which row owns it.

Found by building cert 100031768368 (280mm exactly, band C) in Elmhurst
and comparing every worksheet line to the calculator: volume/ACH/floor/
doors matched exactly, but the wall didn't (1.70 vs Elmhurst's 1.40)
despite an identical input crosswalk. Initially reverted a first attempt
at this fix when it appeared to regress an already-pinned cert
(217091901, band A, also nominally 280mm, previously "confirmed" at
U=1.70) — but that cert's build script never actually set a wall
thickness field, so its shared Elmhurst assessment had silently
inherited a stale 260mm from an earlier build. Fixed that build script
and rebuilt with the correct 280mm entry: Elmhurst's worksheet now also
gives U=1.40, matching 100031768368 and confirming the fix rather than
contradicting it.

Both certs move to (near-)exact lodged matches: 100031768368 59.12 ->
61.21 (lodged 61, within 0.5); 217091901 60.82 -> 61.59 (lodged 62,
exact). Corpus gauge 77.8% -> 78.6% within-0.5, MAE 0.636 -> 0.627 (14
corpus certs lodge exactly 280mm solid brick). TDD'd, 46 pins + full
suite green (2310 passed).

Co-Authored-By: Claude Fable 5 <noreply@anthropic.com>
2026-07-03 12:25:07 +00:00
..
uprn_47084930 test(accuracy): ratchet 77.3% -> 77.7% via flat-roof insulation-thickness fix (Elmhurst-validated) 2026-07-02 23:27:57 +00:00
uprn_74061136 test(accuracy): ratchet SAP MAE 0.668 -> 0.658 via instantaneous-electric-DHW off-peak fix 2026-07-02 20:04:58 +00:00
uprn_103001004 test(accuracy): ratchet 74.2% -> 75.5% via 'insulated (assumed)' roof Table-18 fix 2026-07-02 19:06:26 +00:00
uprn_217091901 fix(rdsap): RdSAP 10 Table 13 200/280mm solid-brick wall boundary 2026-07-03 12:25:07 +00:00
uprn_4510053280 test(accuracy): corpus-1000 campaign ledger + C001 4510053280 pinned 75 (lodged-software PSR gap) 2026-07-02 18:28:20 +00:00
uprn_10012334488 test(accuracy): pin code-195 electric storage-boiler certs as spec-faithful (§12 Rule 2) 2026-07-03 04:55:42 +00:00
uprn_10013924849 Add SAP-18.0.0 + SAP-16.0 schema coverage; autonomous-run triage findings 2026-06-16 20:04:43 +00:00
uprn_10023443426 sap score and elmhirst mapper optimsaiation 2026-06-20 07:25:42 +00:00
uprn_10070056075 test(accuracy): pin 100051051866 + 10070056075 (clean single-main loop complete) 2026-07-03 04:30:22 +00:00
uprn_10091578598 test(accuracy): pin code-195 electric storage-boiler certs as spec-faithful (§12 Rule 2) 2026-07-03 04:55:42 +00:00
uprn_10094975827 test(accuracy): ratchet 74.2% -> 75.5% via 'insulated (assumed)' roof Table-18 fix 2026-07-02 19:06:26 +00:00
uprn_100031768368 fix(rdsap): RdSAP 10 Table 13 200/280mm solid-brick wall boundary 2026-07-03 12:25:07 +00:00
uprn_100040550095 docs(ledger): re-rank at 77.0% + triage electric-tariff & fabric tail 2026-07-02 19:48:10 +00:00
uprn_100050355518 test(accuracy): ratchet 75.5% -> 77.0% via secondary-fuel collision fix on cost path 2026-07-02 19:43:31 +00:00
uprn_100050881708 chore(hyde): fix window-grid automation (keep good row, delete stale below) + pin 100050881708 2026-07-03 03:55:48 +00:00
uprn_100051051866 test(accuracy): pin 100051051866 + 10070056075 (clean single-main loop complete) 2026-07-03 04:30:22 +00:00
uprn_100061275133 chore(hyde): fix 100061275133 Elmhurst build — 0 fans + PCDB exact boiler 2026-07-03 09:20:12 +00:00
uprn_200004017091 test(accuracy): ratchet 77.0% -> 77.3% via unsized-cylinder storage-loss fix 2026-07-02 23:02:27 +00:00
uprn_200004296092 docs(elmhurst): validate slice-5 wall fix against accredited Elmhurst worksheet (uprn 200004296092) 2026-07-02 20:49:58 +00:00