The API `floor_heat_loss` code is authoritative — confirmed by joining each
single-BP cert's code to its independent `floors[].description` (which the
gov register publishes alongside the code):
code 1 ↔ "To external air" (exposed, 9/9)
code 2 ↔ "To unheated space" (semi-exposed, 6/6)
code 3 ↔ "(other premises below)" (partially htd, 9/9)
code 6 ↔ "(another dwelling below)" (party, 176/176)
code 7 ↔ "Solid"/"Suspended …" (ground, all)
Code 3 was mis-mapped to "To unheated space" (semi-exposed) and, on
mid-/top-floor flats, had its floor area zeroed entirely by the
dwelling-level exposure heuristic. RdSAP 10 §3.12 (PDF p.25) classes a
flat's floor over non-domestic "other premises … heated, but at different
times" as "above a partially heated space" → the §5.14 (PDF p.47) constant
U=0.7 W/m²K — distinct from semi-exposed (Table 20) and party (no loss).
Fix: the mapper sets `is_above_partially_heated_space` on the floor=0
dimension for code 3 (string → "(other premises below)" for fidelity), and
the heat-transmission step lets that per-BP lodgement override the flat
suppression upward (mirroring the existing exposed / "another dwelling
below" overrides). The cascade already routes is_above_partial → U=0.7.
Re-pins golden cert 7536-3827: its Ext2 (bp3) lodges code 3, but the cert's
lossy `floors[]` summary dropped that description, so a prior agent guessed
"code 3 = ground" (U=1.12) and concluded the residual was an irreducible
"register-rounding" artifact. It was this bug: Ext2 floor U 1.12 → 0.70,
PE -6.1952 → -5.6414, CO2 -0.1639 → -0.1492 (both toward 0), SAP unchanged.
Eval: 909 computed, 45.1% → 45.3% within 0.5, mean|err| 1.702 → 1.659,
<1.0 59.5% → 60.2%. 13 code-3 certs improve (0380 +3.71 → -0.63, 0350
+7.82 → +0.83, 2610 +7.47 → -1.29); the few that overshoot were already
failing and carry independent fabric bugs (9763's walls = 8 W/K for 60 m²).
Co-Authored-By: Claude Opus 4.8 <noreply@anthropic.com>
A mid-/top-floor flat whose lowest floor is lodged as an exposed floor
(API floor_heat_loss=1) had its floor area zeroed by the dwelling-level
exposure heuristic, which keys only on the flat label and defaults
has_exposed_floor=False (assuming the floor sits over another *heated*
dwelling). RdSAP 10 §3.12 (PDF p.25) is explicit:
"Otherwise the floor area of the flat ... is:
- an exposed floor if there is an open space below"
i.e. a flat cantilevered over a passageway IS a heat-loss floor on
Table 20. The per-BP `is_exposed_floor` lodgement is authoritative and
now overrides the dwelling-level suppression upward, mirroring the
existing "another dwelling below" party override (which suppresses
downward). The code-1↔"E To external air" enum is confirmed by the
paired API+Summary worksheet certs (0350, 3800).
Eval: 45.1% → 45.3% within 0.5 (909 computed); cert 3836 +6.79 → +0.77,
5717 +1.31 → -0.07 and 0997 +0.76 → +0.05 cross into <0.5. Two
already-failing under-rated certs (7636, 2241) shift further — both are
dominated by independent cost-side over-counts the exposed floor merely
unmasks (7636 walls = 8.98 W/K for 33.87 m² is the real defect).
Co-Authored-By: Claude Opus 4.8 <noreply@anthropic.com>
main_heating_category=9 (warm-air systems, NOT heat pump) had no entry
in _SECONDARY_HEATING_FRACTION_BY_CATEGORY, so a warm-air main with a
lodged secondary raised UnmappedSapCode in
_secondary_heating_fraction_for_category — the last calc_raise in the
API sample (cert 0380-2197-2590-2996-2715: warm air mains gas code 506 +
electric room-heater secondary).
SAP 10.2 Table 11 (p.188): a gas/oil warm-air unit falls under "All gas,
liquid and solid fuel systems" (0.10), and electric warm air under
"Other electric systems" (also 0.10) — so 0.10 regardless of fuel. The
warm-air efficiency (Table 4a code→eff: 506→0.70) and Table 4f fan
energy were already wired; this was the only missing dispatch entry.
0380 now computes: SAP 78.1 vs lodged 77 (+1.1; the residual is per-cert
fabric/PV, not the warm-air dispatch — a faithful 0380 worksheet isn't
available, sim case 28 diverges at SAP 57 / code 502 / condensing unit).
Eval: zero raises remain, computed 908→909; mean|err| 1.703→1.702.
Regression green (2448 pass incl. golden 6035 + cohort); pyright
net-zero (44=44).
Co-Authored-By: Claude Opus 4.8 <noreply@anthropic.com>
SAP 10.2 Table 3 (PDF p.160) names "Direct-acting electric boiler"
verbatim in the primary-loss zero list (alongside electric immersion,
combi, CPSU, integral-vessel heat pump). RdSAP 10 §12 (p.62) classifies
SAP code 191 as the direct-acting electric boiler. Its cylinder is
immersion-heated with no primary pipework, so no primary circuit loss
applies — but `_primary_loss_applies` had no 191 branch, so a 191 main
(main_heating_category 2, "Boiler and radiators, electric") fell through
to the cat-{1,2} boiler branch and accrued ~1177 kWh/yr of phantom
primary loss on the electric-flat segment.
Validated against the cert-2474 worksheet: §4 (59) primary loss = 0,
(64) HW output 1760 (cylinder) + (64a) shower 581. Cert 2474 HW kWh
3585 → 2408; SAP 64.66 → 70.35 (the residual to the lodged 78 is an
Unknown-meter data-fidelity artifact — the register recorded meter_type=3
"Unknown" but the lodged rating used an 18-hour off-peak meter, per RdSAP
§12 / the example worksheets).
Eval mean|err| 1.720 → 1.708 (headline 45.0%, flat ±1 cert — the
electric-flat segment is dominated by the meter data-fidelity artifact).
Regression green (2448 pass incl. golden 6035 + ASHP cohort 1e-4);
pyright net-zero.
Co-Authored-By: Claude Opus 4.8 <noreply@anthropic.com>
When DHW is heated by the main heat pump (WHC 901/902/914 = "from main
system") and the main carries a PCDB Table 362 record,
`_hot_water_fuel_cost_gbp_per_kwh` billed the electric HW at 100% off-peak
low rate (its long-standing TODO). SAP 10.2 Table 12a Grid 1 WH column
(PDF p.191) puts HP-DHW on the ASHP/GSHP-from-database row: 0.70
high-rate fraction at 7-hour and 10-hour → 0.70×14.68 + 0.30×7.50 =
12.526 p/kWh (10-hour), not 7.50 p. The low-rate collapse over-credited
the cat-4 HP-DHW cluster.
Fix: pass the cert WHC into the helper and, for HP-DHW (WHC ∈ {901,902,
914} + PCDB-HP main), bill at the ASHP_APP_N WH blended rate. Electric
IMMERSION (WHC 903) is a different Table 12a row (off-peak immersion 0.17
/ Table 13) and stays on the 100%-low-rate fallback until that slice
lands.
cat-4 cluster (20 certs): mean|err| 2.43→2.11, mean signed +0.06→-0.52
(now per-cert scatter, no systematic bias); cert 9472 +6.4→+3.2, 2789
+6.8→+4.0, 4135 +2.7→within 0.5. Headline mean|err| 1.727→1.720.
Regression green (2447 pass incl. golden 6035 + ASHP cohort at 1e-4);
pyright net-zero.
Co-Authored-By: Claude Opus 4.8 <noreply@anthropic.com>
A heat pump that resolves via its PCDB Table 362 index alone (API path,
data_source=1, no Table-4a SAP code) had sap_main_heating_code=None, so
`_table_12a_system_for_main` fell through the 211-227/521-524 code-range
gate to None → the "100% off-peak low-rate" fallback. On a Dual meter
(RdSAP §12 Rule 3 routes heat pumps to the 10-hour tariff) this billed
space heating at 7.50 p/kWh instead of the SAP 10.2 Table 12a Grid 1
(PDF p.191) ASHP/GSHP-from-database row: 0.80 high-rate fraction →
0.80×14.68 + 0.20×7.50 = 13.244 p/kWh. The collapse over-credited the
whole cat-4 heat-pump cluster.
Fix: route any main with a PCDB heat-pump record to ASHP_APP_N regardless
of SAP code (a Table 362 record IS an Appendix-N heat pump by
definition). ASHP_APP_N and GSHP_APP_N share the 0.80 SH fraction at
7h/10h, so ASHP_APP_N is the canonical Appendix-N row for the SH split.
cat-4 cluster (20 certs): within-0.5 45%→50%, mean signed +1.43→+0.06,
mean|err| 3.81→2.43; cert 9472 +15.0→+6.4, 2789 +13.4→+6.8. Headline
45.0%→45.1%, mean|err| 1.757→1.727. Regression green (only the
pre-existing test_total_floor_area fails); pyright net-zero.
Co-Authored-By: Claude Opus 4.8 <noreply@anthropic.com>
Electric storage heaters (and CPSU) charge overnight and cannot run
economically on a single rate, so their presence is physical evidence the
dwelling is on an off-peak tariff. RdSAP 10 §12 (PDF p.62) applied Rules
1-4 only for a Dual meter; an "Unknown" (code 3) meter returned STANDARD
without consulting the heating type, so a cat-7 storage main billed its
overnight charge at the standard 13.19 p/kWh instead of the 7-hour low
rate (5.50 p/kWh) — ~2.4x too high → large under-rate.
Two coupled fixes:
- `rdsap_tariff_for_cert`: for an Unknown meter, infer the off-peak tariff
from a Rule-1 CPSU (→10-hour) or Rule-2 storage (→7-hour) main; keep
STANDARD otherwise. Direct-acting/room heaters/heat pumps (Rule 3) are
NOT off-peak evidence (run on demand, exist on single-rate meters) so
they stay STANDARD — billing them 100% at the low rate over-credits.
- `_fuel_cost` now resolves its tariff via the §12-aware `_rdsap_tariff`
(not the raw `tariff_from_meter_type`), so the off-peak branch fires for
these storage certs and the legacy scalar fields bill the low rate.
Mirrors `_is_off_peak_meter`'s existing Unknown+electric heuristic (which
already routes HW/secondary off-peak), closing the main-space-heating gap.
Meter-3 electric cluster: mean |err| 11.18 → 6.52, within-1.0 3 → 5 (cert
7336 -26.1 → -0.16, 0380 -19.9 → +1.0). Eval headline 44.9% → 45.0%, mean
|err| 1.82 → 1.76, mean signed -0.08 → +0.02. A few storage certs overshoot
(other residuals the standard rate was masking).
Co-Authored-By: Claude Opus 4.8 <noreply@anthropic.com>
The main pitched/flat roof U-value was derived from the JOINED text of
every roofs[] entry. A room-in-roof carries its own §3.9/§3.10 shell
area + U-value cascade (Table 17 / Table 18 col 4), so a multi-roof cert
lodged "Pitched, insulated (assumed) | Roof room(s), no insulation
(assumed)" leaked the RR's "no insulation" marker into the main roof's
u_roof → U=2.30 applied to the WHOLE main roof, ~3x over-stating its heat
loss. This is the 4700-family regular-roof-U leak.
`_joined_main_roof_descriptions` drops "Roof room(s)" entries before the
main-roof u_roof, falling back to the unfiltered join only for pure-RR
dwellings (every entry an RR) to preserve their prior behaviour. The RR
shell U is unaffected (computed separately) — golden 6035 stays green.
RR-leak cluster (18 certs, RR "no insulation" + a non-RR primary roof):
mean |err| 6.14 → 4.85, within-1.0 0 → 8, within-0.5 0 → 3. Eval headline
44.8% → 44.9%, mean |err| 1.851 → 1.824, mean signed -0.152 → -0.081. Two
certs overshoot (other residuals the leak was masking); the spec rule is
applied uniformly.
Co-Authored-By: Claude Opus 4.8 <noreply@anthropic.com>
A floor lodged API floor_heat_loss=6 ("another dwelling below") sits over
another heated dwelling, so it is a party floor with no heat loss (RdSAP
10 §3). The mapper mapped code 6 → None and the heat-transmission step
drove floor exposure solely from the dwelling-level `has_exposed_floor`
flag — which is keyed only on the dwelling_type label and defaults a
"Ground-floor flat" to an exposed floor. So a ground-floor flat above a
basement dwelling kept its full ground-floor heat-loss area.
Map code 6 → "(another dwelling below)" (still != "Ground floor", so the
§5 (12) suspended-timber rule stays inert) and have the cascade suppress
that BP's floor when its floor_type carries the signal, mirroring the
roof's existing "another dwelling above" per-BP party override.
Cert 2115-4121-4711-9361-3686 (ground-floor flat, floor_heat_loss=6):
floor_w_per_k 47.85 → 0; SAP -23.44 → -4.41. Cert 0350-…-6435 -12.38 →
-0.55; 0926-…-9024 -2.35 → -0.82. Eval mean |err| 1.982 → 1.944.
Co-Authored-By: Claude Opus 4.8 <noreply@anthropic.com>
A 440 mm (>420 mm) solid brick AS-BUILT wall computed U = 1.70 (the
220 mm bucket default) instead of the RdSAP-correct 1.10. The §5.7
Table 13 thickness path only fired for *insulated* brick (external/
internal + thickness > 0); the as-built case fell through to the
Table 6 cavity/solid age-band default.
Spec: RdSAP 10 Specification (9th June 2025), §5.7 "U-values for
uninsulated brick walls, age bands A to E", Table 13 (PDF p.40):
≤200 mm → 2.5, 200–280 mm → 1.7, 280–420 mm → 1.4, >420 mm → 1.1.
Table 6 footnote (b) on the "Solid brick as built" row (PDF p.40):
"Or from 5.7 if wall thickness is other than 200mm to 280mm" — the
thickness table supersedes the flat 1.7 default whenever a documentary
wall thickness is lodged (200–280 mm gives 1.7 either way). The §5.8 /
Table 14 dry-lining R is added on top only when the wall is dry-lined,
per the §5.7 closing sentence.
Validated against the user-generated Elmhurst worksheet "simulated
case 21" (replica of API cert 2818-3053-3203-2655-9204: mid-terrace,
age band B, solid brick as-built 440 mm, room-in-roof). New §3 cascade
pin `test_section_3_wall_u_by_thickness_case21_match_pdf` routes the
Summary through the real extractor + mapper and pins:
(31) 155.1000, (33) 175.6208, (36) 23.2650, (37) 198.8858 — all 1e-4.
External walls Main U → 1.1000; Sheltered RR gable → 1/(1/1.10+0.5) =
0.71 (was 0.92). Pinned on §3 only (case-6 precedent): its code-908
instantaneous multi-point gas water heater has a separate §4 (219) gap.
Cross-check: sim case 20 (220 mm) stays at 1.70 — unchanged.
API SAP accuracy (scripts/eval_api_sap_accuracy.py, 896 computed certs):
% |err| < 0.5 SAP vs lodged: 42.6% → 43.8%; mean |err| 2.045 → 2.010.
Regression: tests/domain/sap10_calculator/ (1861), backend/
documents_parser/tests/ (574), datatypes/epc/ + rdsap golden fixtures
all green (pre-existing test_total_floor_area excepted). pyright strict
net-zero. No solid-brick fixture pin shifted (200–280 mm unchanged).
Co-Authored-By: Claude Opus 4.8 <noreply@anthropic.com>
The 2026 API sample raised UnmappedApiCode on `gable_wall_type` 2 (10 certs)
and 3 (4 certs) — the two RR gable variants beyond Party(0)/Exposed(1).
Sim case 21 (an Elmhurst replica of API cert 2818-3053-3203-2655-9204:
gable_wall_type_1=2, gable_wall_type_2=3) lodges them as "Sheltered" and
"Connected", confirming **2=Sheltered, 3=Connected**.
- Mapper: `_API_TYPE_1_GABLE_TYPE_TO_KIND` gains 2 → `gable_wall_sheltered`,
3 → `connected_wall` (U=0, area deducts — already handled).
- Calculator: new `gable_wall_sheltered` branch. The API path lodges no
per-gable U, so the cascade DERIVES it as RdSAP 10 Table 4 (p.22)
Sheltered = 1/(1/U_wall + 0.5) — back-solved + validated against case 21
(U_wall 1.10 → 0.71) and case 20 (1.70 → 0.92). A lodged U (Summary path)
still rides through as an override.
API sample: 14 raises clear → `computed` 882 → 896, `raise:ValueError` 16 → 2.
Summary path unchanged (Sheltered stays `gable_wall_external` + lodged U, so
cert 000487's hand-built fixture is untouched). 2861 pass (lone
test_total_floor_area pre-existing); pyright strict net-zero (32=32 / 12=12).
NOTE: the derived Sheltered U on cert 2818 lands at 0.92 not 0.71 because the
cascade computes its 440 mm solid-brick wall U as 1.70 (the 220 mm default) —
a SEPARATE wall-U-vs-thickness bug (next slice, validated by case 21's 1.10).
Co-Authored-By: Claude Opus 4.8 <noreply@anthropic.com>
Locks sim case 20 (storage heaters + Detailed RR + loose-jacket cylinder)
as a golden vector: _elmhurst_worksheet_001431_case20.build_epc() routes the
Summary PDF through extractor → mapper → calculator, registered in
test_e2e_elmhurst_sap_score with all 11 SapResult headline pins at 1e-4.
10 pinned exact off slices 1-2 (window extractor, RR stud walls); this slice
closes the last one, co2_kg_per_yr (was 3797.62 vs (272) 3815.4060).
Root cause: on a dual-rate (E7) meter the CO2 path ignored the tariff's
high/low Table-12 electricity codes that the cost path already uses:
- Secondary (direct-acting portable heaters, on-peak) keyed the monthly
Table 12d cascade on standard code 30 (0.15405) instead of the E7 HIGH
code 32 → (263) 0.1616. SAP 10.2 Table 12a Grid 1 direct-acting electric
is 100% high-rate; mirrors the cost side billing it at 15.29 p/kWh.
- Main storage heaters fell through `_table_12a_system_for_main`=None to
the FLAT annual factor (0.136) rather than the dual-rate LOW code: per
the Table 12a design intent ("storage … 100% low rate") they charge
off-peak → E7 LOW code 31 → (261) 0.1357.
case-20 co2 now EXACT. 2433 calculator + 112 golden + documents_parser tests
pass — no dual-meter/storage cohort regression; pyright strict net-zero (32=32).
Co-Authored-By: Claude Opus 4.8 <noreply@anthropic.com>
The fuel codes the calculator now puts on SapResult are its own codes — raw
gov-API enums or already-Table-32, depending on the source mapper (ADR-0015).
sap_code_to_fuel now runs the code through table_32.to_table_32_code
(promoted from private _to_table_32_code) — T32-first, then API-translate,
the SAME normalization the calculator's pricing/CO2 helpers use — before the
Table-32 -> Fuel dispatch, so the bill's carrier matches what the calculator
billed (incl. the API/T32 collision codes, e.g. 20 = wood-logs not heat-net).
Falls back to the raw code for billing fuels the price table omits (the 41-58
heat-network range), which resolve to HEAT_NETWORK -> UnpricedFuel — stricter
than, and intentionally divergent from, the calculator's lossy
default-to-mains-gas for an unpriced code (ADR-0014 §5).
Co-Authored-By: Claude Opus 4.8 <noreply@anthropic.com>
ADR-0014 BillDerivation attributes each end-use (HEATING / HOT_WATER /
SECONDARY / APPLIANCES / COOKING) to a fuel carrier and credits PV
export. SapResult already carried the per-end-use kWh but not WHICH
fuel each end-use burns, nor the annual exported kWh — so a downstream
SapResult->EnergyBreakdown adapter could not pick the right tariff.
Surfaces five output-only fields, threaded exactly like the recently
merged appliances/cooking change (2f039aeb):
main_heating_fuel_code RdSAP10 Table 32 / SAP 10.2 Table 12 fuel
main_2_heating_fuel_code code column (the lodged fuel code, e.g.
secondary_heating_fuel_code mains gas 26). None when the corresponding
hot_water_fuel_code system is absent / fuel not resolvable.
pv_exported_kwh_per_yr SAP 10.2 Appendix M1 §3-4 annual export kWh
(0.0 when no PV).
cert_to_inputs.py populates the four fuel codes from the existing
resolvers the cost/CO2 cascade already uses — `_main_fuel_code`,
`_secondary_fuel_code`, `_water_heating_fuel_code` (not reinvented);
Main 2 is the second `main_heating_details` entry, guarded for length.
There is a single CalculatorInputs construction site (cert_to_demand_
inputs delegates to cert_to_inputs). `pv_exported_kwh_per_yr` already
existed on CalculatorInputs; SapResult collapses its Optional to 0.0.
HARD CONSTRAINT honoured — output-only, zero rating drift. These fields
do NOT feed ECF / total_fuel_cost_gbp / co2_kg_per_yr / primary_energy_*
/ sap_score / any monthly value. Every golden-fixture, Elmhurst e2e
SapResult pin, section cascade pin, and heating-corpus residual stays
byte-identical: calculator suite 1658 -> 1661 passed (+3 new tests),
4 skipped, 0 failed before and after. pyright net-zero (51 -> 51 in
domain/; no new errors in the touched test files).
New tests: a synthetic threading test (four fuel codes + PV export pass
unchanged through calculate_sap_from_inputs; None PV collapses to 0.0)
and a cert-level pin (mains-gas combi cert 000516 -> main fuel code 26,
no Main 2, secondary 30, HW 26). Synthetic CalculatorInputs / SapResult
fixtures updated for the new SapResult fields (defaults cover Inputs).
Co-Authored-By: Claude Opus 4.8 <noreply@anthropic.com>
PR feedback (dancafc): the SQLModel column was Optional[str], but the
domain `SapBuildingPart.wall_insulation_thickness` is Optional[Union[str,
int]] — `_api_resolve_wall_insulation_thickness` returns an int mm when the
API lodges `wall_insulation_thickness == "measured"` (SAP 10.2 §5.7 /
Table 8). The plain str column round-trips that int back as the string
"100", corrupting the Table 8 insulated-wall U-value lookup.
This column was missed in the round-trip-fidelity §1 JSONB sweep
(#1129) — its `Union[str, int]` sibling `roof_insulation_thickness` was
converted, but `wall_insulation_thickness` was not, and no 21.0.0/21.0.1
fixture lodges "measured" so the gap stayed latent. Convert to JSONB
(matching `roof_insulation_thickness` / `flat_roof_insulation_thickness`),
align the column type to Optional[Union[str, int]] (also removes a pyright
type-mismatch), record it in the migration doc §1, and add a round-trip
guard test asserting an int survives as an int (fails as '100' == 100 on
the old str column).
Co-Authored-By: Claude Opus 4.8 <noreply@anthropic.com>
SAP 10.2 Appendix G4 (PDF p.72-73). A PV diverter routes surplus PV
generation (the would-be export EPV,m × (1 − βm)) to an immersion heater
in the hot-water cylinder. Per G4 step 4:
SPV,diverter,m = EPV,m × (1 − βm) × 0.8 × fPV,diverter,storageloss
(0.8 = cylinder heat-acceptance; fPV,diverter,storageloss = 0.9 for the
higher storage temperature), clamped to ≤ (62)m + (63a)m, and entered as
the negative worksheet (63b)m (step 5). The β factor is computed on the
PRE-diverter (219) per the §3a note (lines 5485-5486). Effects:
- (64)m = (62)m + (63b)m → less main-system water-heating fuel (219);
- export drops to EPV,ex,m = EPV,m(1 − βm) + (63b)m / 0.9 (§4 p.94
line 5501); the onsite dwelling portion EPV,m × βm is unchanged.
Inclusion (G4 step 1) requires ALL of: a PV system connected to the
dwelling; a cylinder larger than (43) average daily HW use; no solar
water heating; no battery — else the diverter is disregarded.
Three layers:
- extractor reads Summary §19 "Diverter present"; schema 21.0.0/21.0.1
SapEnergySource gains `pv_diverter` (API `sap_energy_source.pv_diverter`);
- `Renewables.pv_diverter_present` + domain `SapEnergySource.pv_diverter_present`,
set in both the Elmhurst and API mapper paths;
- `_pv_diverter_monthly_kwh` applies the G4 math after the β split;
`cert_to_inputs` recomputes (219) and the PV export.
On simulated case 19 (electric storage heaters, 7-hour, PV + diverter):
SAP continuous 50.33 → 51.34 (worksheet 51.2221; both round to the
lodged 51), cost (255) 1847.5 → 1812.3 (ws 1816.6), CO2 (272) 3331 →
3120 (ws 3126), with (233a) dwelling 1280.6 (ws 1280.4). The residual
+0.11 SAP is an upstream winter Appendix-M monthly-EPV-shape gap +
fabric (33) +1.0, tracked as the next case-19 cause. Suite: 2412 pass.
Co-Authored-By: Claude Opus 4.8 <noreply@anthropic.com>
SAP 10.2 Appendix M1 §6 (PDF p.94, lines 5510-5513): "apply the normal
import electricity price to PV energy used within the dwelling and the
'electricity sold to grid, PV' price from Table 12 to the energy
exported. In the case of the former, use a weighted average of high and
low rates (Table 12a)."
`_pv_dwelling_import_price_gbp_per_kwh` was returning the bare off-peak
LOW rate (5.50 p/kWh on a 7-hour tariff) for the PV-used-in-dwelling
credit. PV self-consumption displaces the dwelling's "all other uses"
electricity (lighting / appliances / pumps), which on an off-peak tariff
bills at the Table 12a Grid 2 ALL_OTHER_USES weighted blend, not the low
rate. On simulated case 19 the worksheet (252)/(269) credits
PV-used-in-dwelling at 14.3110 p/kWh = 0.90 × 15.29 + 0.10 × 5.50; we
credited it at 5.50, under-crediting onsite PV by ~£0.088/kWh on every
off-peak PV cert.
Fix delegates to `_other_fuel_cost_gbp_per_kwh(tariff, prices)` (the same
ALL_OTHER_USES rate): STANDARD tariff still returns the flat Table 32
code 30 13.19 p/kWh (golden cohort unchanged — all 2412 tests pass);
off-peak returns the weighted high/low blend. Call sites now pass the
resolved `_rdsap_tariff(epc)`. The now-unused
`_off_peak_low_rate_gbp_per_kwh_via_meter_heuristic` (its only caller)
is removed.
Co-Authored-By: Claude Opus 4.8 <noreply@anthropic.com>