Walked the worksheet section-by-section (dimensions, ventilation, fabric,
internal/solar gains, MIT, space-heating requirement, fuel cost) against
the calculator's matching intermediates. Internal gains and heat loss
matched closely, but solar gains (worksheet line 83) was 2.2x off in
January (56.9 W vs our 123.4 W) — traced to the Elmhurst BUILD entering
all 12 real windows (3 orientations: NW 7.05 m2, NE 1.21 m2, SE 7.06 m2)
as a single synthetic 15.32 m2 "North" group, understating solar gain.
Verified by reproducing both build artifacts in the calculator: real
windows + real Table-11 gating = 76.33 (our answer, matches lodged 76
exactly); collapsing to a synthetic single-North window + forcing Table
11 on = 72.62, reproducing Elmhurst's 72 almost exactly. Confirms neither
residual is a mapping or calculator bug — one is a deliberate,
regression-tested spec choice (Table 11) and the other is an artifact of
how this specific Elmhurst reconciliation build was entered.
Co-Authored-By: Claude Fable 5 <noreply@anthropic.com>
The prior comment blamed a stale build-side combi artifact (already fixed
this session) and my earlier conversational claim that Elmhurst's overall
SAP used regional weather was wrong too — verified the worksheet's (5)
dwelling volume and wind table match our UK-average rating cascade exactly.
The actual, now-quantified driver: Elmhurst's worksheet (201)/(202)/(215)
show it unconditionally applies SAP 10.2 Table 11's 10% secondary/portable-
electric-heater fraction based on main heating category alone, with no
secondary lodged on the cert. Our `_secondary_fraction` deliberately gates
this on an actual lodged/forced secondary (see the adjacent S-B30 note:
applying it unconditionally regressed the full 1000-cert corpus MAE by
+0.16). Forcing Table 11 on for just this cert moves 76.33 -> 73.62 (~62%
of the 76.33-vs-72 gap) — confirms this, not a mapping error, drives the
residual. Documented so the next reader doesn't re-litigate it.
Co-Authored-By: Claude Fable 5 <noreply@anthropic.com>
Per the PR #1439 handoff: swept every cert now sitting at |Δ| in [1.0, 2.0)
(58 certs) using the cost-vs-demand signature bucketer (why_diverge.py's
logic) plus field_bias.py's full-corpus subgroup scan (re-run clean after
the two engine fixes above — no |meanΔ|>=0.5 systematic subgroup with
coherent median).
Breakdown: 17 room-in-roof (already spec-mandated/worksheet-validated per
PRs #1440/#1441), 7 electric cost/tariff variants (spec-faithful vs lodged,
consistent with the diagnosed electric cluster), 4 non-electric cost
residuals (spec-faithful), ~26 non-electric fabric/demand certs. Manually
inspected geometry (floor areas/perimeters/heights, wall/roof codes,
window/door counts) for the 4 largest fabric/demand outliers in the band
(100031768368, 100070450818, 100110097281, 100051051866) — no data-entry
anomaly comparable to the earlier 12109191 decimal-floor-area bug. This
confirms the handoff's "our calc faithful, lodged differs" pattern holds
across the band; no engine bug survived the pass. Notes appended per-cert
in worklist.md (`<-`, preserved by build_worklist.py reruns).
Co-Authored-By: Claude Fable 5 <noreply@anthropic.com>
ADR-0048 records why a system-replacing heating override must emit a
complete companion set — category and control archetype-forced for
coherence, fuel and meter deferred where multiple values are valid, and
an unmapped companion logged rather than silently inherited. Adds the
Heating Companion Set glossary term to CONTEXT.md.
Co-Authored-By: Claude Opus 4.8 <noreply@anthropic.com>
ventilation(): the cert lodges no extract-fan count and RdSAP 10 Table 5's
age-band B default is 0, but the build entered 1 — inflating Elmhurst's own
(8)/(21) infiltration lines relative to both the cert and our engine.
space_heating(): switched from the generic "Combi condens" SAP-Table dialog
code (84% efficiency, no PCDB record) to elmhurst_lib.set_pcdb_boiler(18908)
via clear_main_heating_code — resolves the exact lodged product (Worcester
Greenstar 4000, 88.70%) and its correct keep-hot classification (None),
matching the SAP engine's own PCDB lookup and removing the "Standard Combi"
keep-hot artifact the reused generic code carried.
Also corrected the file's stale docstring (described a different property
entirely — mid-terrace/250mm/DUAL meter/11 windows/lodged 63 — left over
from a copy-paste).
Verified against the refreshed worksheet: (21) shelter-adjusted ACH 0.6938
now EXACT vs our engine's ventilation_from_cert; (61) combi loss monthly
kWh matches ours to ~0.01 kWh (was carrying a ~360 kWh/yr keep-hot artifact).
Both open items from the PR #1439 handoff are resolved.
Co-Authored-By: Claude Fable 5 <noreply@anthropic.com>
A system-replacing override whose category or control is not yet mapped
now logs an error naming the archetype and code, so the incomplete
companion set (which otherwise silently inherits the replaced system's
value) is visible for review — log-and-continue, matching flag_fuel_mismatch.
Co-Authored-By: Claude Opus 4.8 <noreply@anthropic.com>
Control 2601 (SAP Table 4e Group 6 room-heater, +0.3 C conservative
default) now overlaid for electric room heaters, matching the gas/oil/
solid siblings, so a replaced storage heater's manual charge control
2401 (+0.7 C) no longer survives and over-warms the modelled dwelling.
Co-Authored-By: Claude Opus 4.8 <noreply@anthropic.com>
_has_suspended_timber_floor_per_spec only read the Main bp's per-part
floor_construction_type lodgement; the gov-API mapper frequently leaves
that None even when the global epc.floors[].description carries an
explicit "Suspended, ..." observation. _main_floor_u_value already fell
back to this joined description for the U-value calc — the infiltration
rule did not, so a genuinely suspended-timber floor silently entered
(12)=0 instead of 0.2 unsealed. Extracted the shared
_effective_floor_description helper and added a tri-state resolver
(explicit lodgement -> description, excluding "not timber" -> Table 19
footnote-1 age-A/B default) so both paths agree.
Cert 100061275133 (Elmhurst-validated build, PR #1439 handoff): engine
77.24 -> 76.33, now an exact match to lodged (76). Corpus gauge 77.7% ->
77.8% within-0.5, MAE 0.637 -> 0.636; floors ratcheted.
Co-Authored-By: Claude Fable 5 <noreply@anthropic.com>
Category 10 (SAP Table 4a Room heaters) now overlaid for electric room
heaters (691-701), so a replaced storage heater's category 7 no longer
survives onto the effective cert and mis-bills via the Table 12a resolver.
Co-Authored-By: Claude Opus 4.8 <noreply@anthropic.com>
Cracks the 'PCDB disabled' blocker. The PCDF boiler reference resolves the exact
lodged boiler (e.g. 18908 -> Worcester Greenstar 4000, 88.70%) when: (1) the main
heating CODE is empty server-side (else the field + magnifying glass are
aspNetDisabled), and (2) the index is entered via REAL keyboard + Tab (a JS-set
.value doesn't survive the AutoPostBack). Now Elmhurst uses the same boiler
efficiency as the SAP engine, so worksheet vs calculator compare like-for-like.
Verified on 100061275133: Elmhurst now shows 'Efficiency of main space heating
system 1 = 88.70%' (was generic 84%). Includes updated worksheet evidence.
Co-Authored-By: Claude Opus 4.8 <noreply@anthropic.com>
Third Playwright-entry error found via input reconciliation: my build left
draught-proofed doors at 0 (Elmhurst computed 33% draught proofing), but the
cert lodges percent_draughtproofed=100. Our calculator correctly uses 100% ->
infiltration 42.66 W/K; the ~19 W/K ventilation gap to Elmhurst was purely my
build error. On matched inputs our fabric+TB (109.38) equals Elmhurst's total
fabric (37) EXACTLY, confirming the calculator is RdSAP-faithful. Committed for
build-faithfulness record; the engine's +1.24 vs lodged 76 is not a bug.
Co-Authored-By: Claude Opus 4.8 <noreply@anthropic.com>
Audits identity pass-through fields (dims, counts, thicknesses) raw cert vs
EpcPropertyData across all 1000 certs. All apparent mismatches are legitimate
mapper behavior the first-pass audit didn't model: window_wall_type=4 windows
correctly split to sap_roof_windows (not dropped); empty placeholder building
parts correctly discarded; 'measured' insulation-thickness sentinel resolved to
the wall_insulation_thickness_measured value. Remaining per-BP diffs were an
index-misalignment artifact (raw BP[i] vs epc BP[i] after empty BP0 dropped).
Conclusion: mapper is faithful; divergences are Playwright-entry or calc-side.
Co-Authored-By: Claude Opus 4.8 <noreply@anthropic.com>
Input reconciliation (Elmhurst summary vs EpcPropertyData vs raw cert) exposed
two Playwright-entry errors: lighting entered as 6 incandescent (cert has 5 LED,
100% low-energy) and wall thickness left at Elmhurst's 260mm default (cert lodges
400mm). Fixing both moved Elmhurst 67->69. Confirmed the MAPPER is faithful
(every fabric/heating/lighting field matches the raw cert) and the engine uses
the correct PCDB 18908 efficiency (88.7%). The remaining Elmhurst gap to lodged
76 is the un-enterable PCDB boiler (automation falls back to generic BGW 84% +
keep-hot); the engine (77) is faithful. Not a mapping error.
Co-Authored-By: Claude Opus 4.8 <noreply@anthropic.com>
Field-level bias scan (scripts/corpus_1000/field_bias.py) flagged solid-brick +
internal-insulation certs (wall_con+ins=(3,3)) systematically under-rating
(median -0.40, n=18). Root cause: _insulation_bucket routed insulation that is
KNOWN PRESENT but with a thin lodged thickness (5-24mm, below the smallest
tabulated 50mm column) to bucket 0 (uninsulated, U 1.7) - WORSE than the
present-but-unknown case, which the RdSAP Table 6 footnote correctly routes to
the 50mm row. A known 10mm shouldn't read as higher-U than not knowing at all.
Now present insulation never falls to bucket 0; thin/unknown thickness both
round up to the 50mm row. Only genuinely absent insulation maps to 0.
Corpus cert 5117280 (10mm internal, no wall thickness -> bucket path): Δ -4.44
-> +1.08. Corpus MAE 0.641 -> 0.637, PE MAE 3.0 -> 2.9. Gauge 77.7% holds; 44
RealCert pins + 342 fabric tests green. TDD: 2 new unit tests.
Co-Authored-By: Claude Opus 4.8 <noreply@anthropic.com>
Added scripts/corpus_1000/demand_cohort.py (isolates fabric/demand-driven
divergences from cost noise). Investigation conclusion: the demand-side tail is
one-offs, not a cluster. 12109191 (+13.1) is a LODGED decimal error (365.67 m²
floor, 10x its ground floor). 217060420 (-4.4) is spec-faithful (36.6 m2 lodged
glazing at spec U). The only >=3 structural clusters among diverging certs are
electric flats (already diagnosed spec-faithful). No generic fabric bug remains;
gauge 77.7% is near its structural ceiling. Marked 12109191 unbuildable in ledger.
Co-Authored-By: Claude Opus 4.8 <noreply@anthropic.com>
Electric-tariff cluster investigation. The 112-cert electric-main cohort is
mixed-sign within every category/meter - no systematic tariff bias. Root cause
of the biggest non-xfail divergences (10012334488 +13.2, 10091578598 +7.81):
SAP code 195 = 'Electric water storage boiler' (Table 4a p.170), which SAP 10.2
§12 Rule 2 correctly bills mostly at the 7-hour off-peak rate. Both are pure
cost gaps (PE/CO2 match lodged -> demand right); the lodged software over-billed
the storage boilers at peak rate. The engine is SPEC-FAITHFUL - matching lodged
would tune against §12/Table-4a. Pinned to the spec-faithful engine values.
Adds scripts/corpus_1000/elec_cohort.py (electric-main cohort analyzer).
Co-Authored-By: Claude Opus 4.8 <noreply@anthropic.com>
Final two clean single-main gas certs. Both small cost-side residuals (+1.04 /
-1.01 SAP) on cavity-insulated fabric already Elmhurst-validated on sibling
certs, with properly-insulated cylinders (insulation type 1, 50/80mm - not the
type-0/NULL zero-storage-loss bug). No fabric anomaly; the register data fully
explains the engine output. Pinned to observed engine 71 / 79.
Co-Authored-By: Claude Opus 4.8 <noreply@anthropic.com>
2-storey semi, solid brick 400mm with EXTERNAL insulation, 300mm loft,
suspended uninsulated ground floor, gas combi, double glazing (glazed_type 13).
Built in accredited Elmhurst RdSAP10: roof (U 0.14, 5.459 W/K) and windows
(15.32 x eff U 1.3258 = 20.311 W/K) match the engine EXACTLY; the
externally-insulated wall is engine U 0.29 vs Elmhurst 0.30, validating the
slice-5 external-insulation default (100mm added over solid brick); suspended
ground floor engine 0.68 vs Elmhurst 0.70. Elmhurst's overall SAP 67 is not
comparable (reused-assessment Standard-Combi keep-hot loss, a build artifact).
Engine 77 vs lodged 76 (within 1.24). Pinned to the observed 77.
Co-Authored-By: Claude Opus 4.8 <noreply@anthropic.com>
Top-floor flat, solid brick uninsulated, uninsulated flat roof, gas combi,
SINGLE glazing (glazed_type 5). Built in accredited Elmhurst RdSAP10 and every
heat-loss element matches the engine EXACTLY: walls 53.18, flat roof 145.57,
floor 0, party 0, and — with the faithful single glazing — windows 34.7114 W/K
(8.62 m2 x eff U 4.0268). Confirms the mapper's glazed_type 5 -> single (raw U
4.8) is spec-correct per epc_codes.csv, not the double it superficially
resembles. Engine 61 vs lodged 62; the -1.18 is a cost-side residual, not a
fabric bug. Pinned to the observed engine 61.
Co-Authored-By: Claude Opus 4.8 <noreply@anthropic.com>
SOLVED the window-grid blocker (per Junte's "keep one and edit, don't
delete all"): set_single_window now ADDS the fresh window (it inserts at
DOM index 0), then deletes the STALE rows BELOW it by index (high->low,
never index 0) via the per-row Delete image button + JS-clicked Yes modal.
The freshly-added row survives as the single window; no 0.00 junk strands
to block the Recommendations gate. Verified end-to-end: cert 100050881708
built, worksheet downloaded, walls (0.70) + roof (0.19) match the engine
EXACTLY. Combined with the earlier fill+Tab (area postback) + frame/gap
(validation) fixes, the per-cert loop now runs autonomously on clean
single-main certs.
Pin: 100050881708 (semi, cavity filled, pitched 225mm, suspended ground
floor, combi) engine 72 = lodged 70 +2; walls/roof accredited-Elmhurst-
matched. NB the build entered the suspended ground floor as an upper
"above unheated space" floor, so Elmhurst's worksheet SAP (61) is not a
clean comparison — the engine uses the correct §3.12 suspended-ground U
(0.74); the pin rests on the walls+roof match + lodged.
No engine change.
Co-Authored-By: Claude Fable 5 <noreply@anthropic.com>
Continued hardening for the per-cert Elmhurst loop. Confirmed findings:
- The window Width/Height must be set via Playwright .fill() + Tab (fires
the ASP.NET AutoPostBack so the server commits the area); a JS-set of
.value bypasses the postback and Elmhurst persists a 0.00-area row.
- Frame Type (PVC) + Glazing Gap (12 mm) are REQUIRED per row or the
Recommendations gate blocks the worksheet ("Frame Type/Glazing Gap must
be entered"). add_combined_window now sets both.
KNOWN BLOCKER (documented for the next attempt): the window grid is not
yet reliably automatable when stale rows exist on the shared assessment.
New rows insert at index 0; the delete flow reliably removes only index 0
(the newest), so accumulated 0.00 junk rows BELOW cannot be targeted, and
grid reads are timing-inconsistent across postbacks. A robust handler
needs to either (a) drive the per-row Delete by matching the row's
server-side id rather than DOM index, or (b) start each build from a
freshly-created assessment (not the shared one) so the grid is empty.
Until then the per-cert loop runs only on the FIRST build after a manual
window reset. build_100050881708.py is the WIP template.
No engine change.
Co-Authored-By: Claude Fable 5 <noreply@anthropic.com>
Support for the per-cert Elmhurst worksheet loop:
- goto()/save_close(): fall back networkidle -> domcontentloaded on
timeout so an incomplete-validation state (half-set RR, 0-area window)
no longer hangs navigation.
- add_combined_window(): select glazing first (AutoPostBack), then JS
input+change+blur the width/height with settle waits so the Area cell
computes before Add (a plain .fill() raced the postback -> 0.00 row).
- set_single_window(): leave the grid holding exactly one row, deleting
rows carried over from a prior build of the SHARED assessment (the
window grid is the only accumulating page).
- reset_transient_state(): return the shared assessment to neutral after
a run (clear RR age band, secondary = No, meter = Single).
KNOWN RESIDUAL: the window grid still intermittently persists a 0.00 area
through Save & Close (Elmhurst's "each Add wipes the previous row" +
last-row-undeletable behaviour), and the secondary-heating dialog's modal
background can intercept the cascade click. Reliable autonomous grinding of
per-cert builds needs these two hardened further; the loop currently
completes clean single-main gas certs (see the 47084930 flat-roof slice)
but stalls on secondary-heating + stale-window combinations. build_
100021924710.py is the WIP template for that harder shape.
No engine change.
Co-Authored-By: Claude Fable 5 <noreply@anthropic.com>